Manufacturer’s instructions must be left with the unit CRC R106.2
All receptacles installed for the connection of EV charging shall be GFCI-protected CEC 625.54
Disconnect required for EV > 60 amps CEC 625.43 must also comply with CEC 110.25 The means to lock must be an integral part of the enclosure. A portable locking device is NOT acceptable.
New construction ADU does not require an EV charger
Suitable for environment (indoor/outdoor)
Indoor coupling height 18-48”
Outdoor coupling height 24-48”
Cable length 25’ unless equipped with a cable management system
Verify branch circuit conductors sized 125% of max
Provide working clearances at all electrical equipment (36” deep x 30” wide)
Subject to vehicular damage provide bollard (4” diameter steel pipe filled with concrete, ≥ 40” above finished grade, imbedded in footing measuring 12” in diameter and 3’ deep)