(Outdoor) Drowning Prevention Safety Features CRC appendix AX (AV100.2)
- Applies to new or existing remodeled pool/spa at private and single-family homes
One of the following 7 safety features
- Shall be isolated from the home by an enclosure per AV100.3
- Removable mesh pool fence ASTM-F2286 with self-close and latch lockable gate
- Approved safety pool cover ASTM-F1346
- The residence shall be equipped with exit alarms on doors providing direct access to the pool
- All doors with direct access from the home to the pool shall be self-close and latch mechanism ≥ 54” above the floor
- The alarm which will sound off when detecting accidental or unauthorized entrance to the water ASTM-F2208
- Other means that ≥ features 1-4 and have been verified by an approved testing laboratory meeting standards of ASTM
Enclosure Requirements (all of the following)
- Access gates open away from the pool and are self-close+latching (latching device ≥ 5’ above ground)
- Enclosure ≥ 5’ in height
- Enclosure is ≤ 2” off the ground
- Gaps or voids don’t allow passage of ≥ 4” sphere
- The outside surface is free of protrusions or cavities or characteristics that serve as hand holds or foot holds enabling a child to climb over
Pool/Spa Electrical CEC 680
- Equipment rooms/pits must have drainage preventing water accumulation CEC 680.12
- Disconnecting Means: within sight and > 5′ away from the water’s edge
- Water heaters heating elements -subdivide loads ≤ 48 amps and protected at 60-amps. The ampacity of branch circuit conductors and rating of overcurrent shall be not less than 125% of the total nameplate-rated load CEC 680.10
- Underground wiring is prohibited under the pool or within 5’ of the water’s edge. (exceptions where space is limited and wiring is necessary for pool equipment – ok in approved conduit and depth) CEC 680.11
- Utilization equipment: One or more maintenance means of disconnect shall be readily accessible ≥ 5’ away from the water’s edge and within sight of the equipment. CEC 680.13
- Branch circuits feeding pool motors shall be in an approved conduit and have an insulated ground sized per conductor not less than #12 AWG CEC 680.21.A.1
- Outlets 120-240 recept or hardwire shall be GFCI CEC 680.21.C
- Cord and plug (shall be grounding type plug) pool motors 3’ max ECG ≥ 12 AWG CEC 680.21.A.3
- Service receptacle: 1 or more recept on general-purpose branch 6’ – 20’ from the inside edge of the pool (≤ 6’6” above floor, platform, grade)
- Circulation and Sanitation system location – receptacle serving circ and san equipment ≥ 10’ from the inside edge of the pool. Conditions: single receptacle, grounding type recept, GFCI
- Receptacles: (Other than circ and san) – shall be ≥ 6’ from the inside edge of the pool
- GFCI: recept – all recept ≤ 20’ from waters edge CEC 680.22(a)(4)
- Electrically operated pool covers: ≥ 5’ from the water’s edge. Controls are to be located with a full view of the pool. All equipment is listed for wet location. GFCI protected branch circuit.
Lighting/fans
- (OUTDOOR) Luminaire, Light outlets, Ceiling fans – above and within 5’ of the inside edge of the pool ≥ 12’ above the max water level CEC 680.22(B)(1)
- (INDOOR) If GFCI circuit – Luminaire, Light outlets, Ceiling fans- above and within 5’ of the inside edge of the pool ≥ 7’6” above the max water level. Totally enclosed luminaire, listed fan CEC 680.22(B)(2)
- Luminaires wall mounted top of lens ≥ 18” below the water line unless listed for lesser no luminaire shall be 4” below normal water level
- All forming shells with NM conduit shall have provision for terminating an 8 AWG ground except low-voltage
Bonding Min #8 awg w/ listed clamps (Direct Burial)
- Equipotential Bonding of the following:
- 1. Pool shell rebar
- 2. 3’ perimeter surface
- 3. Metallic components
- 4. Underwater lighting
- 5. Metal fittings
- 6. Electrical equipment
- 7. Fixed metal parts
- 8. Pool water 9 sq in CEC 680.26
- Exception: Spa and Hot Tub with all of the following conditions:
- 1. Listed as self-contained for above-ground use
- 2. Not identified as suitable for indoor use only
- 3. Installed per manufacture instructions and located on or above ground
- 4. Top rim of the spa/hot tub ≥ 28” above perimeter surfaces within 30” (above ground spa installed in/on a trenched pad) CEC 680.42(B)(1-4)
Plumbing
- Water supply shall have one of the following: air gap, vacuum breaker, or backflow preventer CPC 603.5.5 CPC 603.5.20
- Waste water pipes shall be installed as indirect waste CPC 813.0
- Pool Heaters shall have a readily accessible on/off switch