- A valid permit and plans must be on-site R106.3.1
- Pole
- 20′ with 4′ in-ground AMP
- PT in ground AMP
- Rectangular or circular in cross-section and shall be solid AMP
- Rectangular poles ≥ 6” × 6” and braced AMP
- The panel must be labeled CEC 110.22.A
- Weatherproof receptacles with in-use, heavy-duty covers CEC 406.9.B.2
- GEC – protected CEC 250.64.B
- 8’ x 5/8″ ground rod with #4 copper CEC 250.52.5
Vertical Clearance for Service Poles: See Service Overhead Clearances in Services
Ampacity Chart: See Ampacity Chart in Services