Temp Power

  • A valid permit and plans must be on-site R106.3.1
  • Pole
    • 20′ with 4′ in-ground AMP
    • PT in ground AMP
    • Rectangular or circular in cross-section and shall be solid AMP
    • Rectangular poles ≥ 6” × 6” and braced AMP
  • The panel must be labeled CEC 110.22.A
  • Weatherproof receptacles with in-use, heavy-duty covers CEC 406.9.B.2
  • GEC – protected CEC 250.64.B
  • 8’ x 5/8″ ground rod with #4 copper CEC 250.52.5

Vertical Clearance for Service Poles: See Service Overhead Clearances in Services

Ampacity Chart: See Ampacity Chart in Services

Link to AMP Temp Power Handout