1-SYSTEM BONDING JUMPER
2-EQUIPMENT GROUNDING CONDUCTOR
3-SUPPLY-SIDE BONDING JUMPER
4-GROUNDING ELECTRODE CONDUCTOR
5-TERMINAL CONNECTOR TO ENCLOSURE
ALWAYS USE EXTREME CAUTION DURING THE INSPECTION OF ELECTRICAL EQUIPMENT, DO NOT PUT YOUR HAND INSIDE THE TRANSFORMERS, AND ALWAYS ASSUME IT IS ENERGIZED!!!
- TRANSFORMERS SHOULD BE LABELED WITH CLEARANCES (< 112.5KVA 12” FROM COMBUSTIBLES UNLESS A BARRIER IS PROVIDED)
- DRY TRANSFORMERS ARE NOT REQUIRED TO BE READILY ACCESSIBLE
DISCONNECTING MEANS CEC450.14
- LOCATED WITHIN SIGHT OR REMOTE LOCATION
- REMOTE DISCONNECT REQUIRED TO BE LOCKABLE
- IF THE DISCONNECT IS REMOTE, THE LOCATION OF THE DISCONNECT SHALL BE MARKED ON THE TRANSFORMER
OVERCURRENT PROTECTION CEC450.3
PRIMARY CALC BELOW (PRIMARY EXAMPLE IS 480 VOLT)
- OCPD RATED AT 125% OF THE LOAD
- X 1.25 = LOAD
- YOU CAN THEN USE THE NEXT HIGHEST RATING OVERCURRENT PROTECTION DEVICE/BREAKER. (OR USE ADJUSTABLE RATE BREAKER)
- EXAMPLE 45KVA=45,000:
- YOU CAN THEN USE THE NEXT HIGHEST RATING OVERCURRENT PROTECTION DEVICE/BREAKER. (OR USE ADJUSTABLE RATE BREAKER)
- NEXT HIGHEST=70AMP
SECONDARY CALC BELOW (SECONDARY ON EXAMPLE IS 240 VOLT)
- EXAMPLE 45KVA=45,000
- YOU CAN THEN USE THE NEXT HIGHEST RATING OVERCURRENT PROTECTION DEVICE/BREAKER. (OR USE ADJUSTABLE RATE BREAKER)
- NEXT HIGHEST = 150 AMP BREAKER
- IN ALL CASES THE CONDUCTORS SHALL BE SIZED BASED ON THE OVERCURRENT PROTECTION DEVICE/BREAKER
GROUNDING CEC 250.30
- SEE EQUIPMENT GROUND SIZED PER TABLE 250.122
- SEE GROUNDING ELECTRODE CONDUCTOR PER TABLE 250.66
- Grounding electrode: A common grounding electrode conductor for multiple separately derived systems shall be permitted. A grounding electrode conductor tap shall then be installed from each system CEC 250.30.6
BONDING CEC250.104
- BOND METAL WATER PIPE CEC 250.104.A
- BOND OTHER METAL PIPING CEC 250.104.B
- BOND STRUCTURAL METAL CEC 250.104.C
- BONDING BUSHING CEC250.9
Transformer Vault: CEC450.42 (typical for large oil/askarel insulated transformers)
- 3 HOUR CONSTRUCTION (1hr if sprinkler/fire protection system) (note: 3hr is typically 6” reinforced concrete)
- 4” CONCRETE SLAB (if floors below approved by E OR)
- OUTSWING DOOR WITH PANIC HARDWARE (3hr rated fire if interior)
- STUD AND WALLBOARD CONSTRUCTION ARE NOT PERMITTED
- SILL OR CURB ≥ 4”
- DOORS SHALL BE LOCKED (ACCESS BEING ALLOWED BY QUALIFIED PERSONS)